The Southeast plant (7.5 mgd design) began operating in June 2005. Jake Callahan, director of operations, describes it as a “conventional activated sludge plant.” Preliminary treatment includes Spiralift screw pumps (Evoqua Water Technologies) and a Waste Tech Model 1300 bar screen with three-eighths-inch separation (Kusters Water, division of Kusters Zima Corp.) followed by a grit trap (Smith & Loveless) and grit washer (Parkson Corp.). The lift stations to the two primary clarifiers use three 125 hp Pentair - Fairbanks Nijhuis pumps. Each clarifier has a Toshiba sludge density meter.
Anoxic tanks are upstream of the five aeration tanks. “They help control the filaments in the activated sludge process,” Callahan says. “We run a higher solids retention time and get good nitrification in winter when the biology slows down. And we don’t observe any settling issues with the biological floc in our secondary clarifiers.” The anoxic tanks have Environmental Dynamics International FlexAir mini-panel fine-bubble diffusers. Blowers are 300 hp Turblex Model KA10SV-GL210 operated with dissolved oxygen control.
Flow then goes to the two 115-foot-diameter center-feed secondary clarifiers for settling. Tertiary treatment consists of a traveling bridge filtration system. Media is anthracite coal on top, followed by coarse and then fine sand. Final effluent is disinfected by a TrojanUV UV4000 system. “This system has worked well, has been stable and is easy to maintain,” Callahan says. Final effluent is discharged to the Little Kickapoo Creek.
The team at the Bloomington-Normal Southeast Plant includes, from left, Tyler Graf, Randy Stein, Tom Anderson, Matt Mink, Caitlin Raasch and Jake Callahan. The plant is named for Callahan’s uncle.Solids are anaerobically digested to Class B standards, thickened and dewatered. Employees apply the material to farmers’ fields within about 30 miles of the plant. “We haul it and we spread it,” Callahan says. “That way they know where it’s been applied and the application rate is correct. Things are going pretty smoothly.” One reason is the SCADA software: “A lot of thought was put into our WIN-911 software, which dials out to the on-call operator when there’s a problem.”
The plant also has a unique post-disinfection treatment stage: An experimental constructed wetland removes nutrients from about half of the plant’s discharge. The wetland has hiking trails and bird-watching sites that make it a getaway for area citizens.
Callahan checks the status of the TrojanUV4000Plus (TrojanUV) disinfection system.Plant managers sent Jon Outlaw, operator, and Tom Anderson, chief mechanic, to run the plant when it started up in 2005. Stein notes that the plant was designed to run with just one operator and two maintenance people. The operator and maintenance person sent to run the plant in 2005 are now nearing retirement.